Provided equipment:
|
Basic UPS signalling RS-232 cable, CD with software, Country-specific detachable power cord, 1 x DC cable, User manual, USB cable |
|
Number of tare power:
|
28 W |
|
Number of power module free slots:
|
0 |
|
Number of power module filled slots:
|
0 |
|
Redundant:
|
No |
|
UPS size:
|
WS |
|
Cable length:
|
1.50 M |
|
Colour:
|
Black |
|
Dimension:
|
23.8 x 40 x 29 Cm (H x D x W) |
|
Net weight:
|
24 Kg |
|
USB compatible:
|
No |
|
Network frequency:
|
40 to 70 Hz |
|
Plug standard:
|
IEC 60320 C14 |
|
Input voltage limits:
|
110 to 285 V adjustable (half load), 160 to 280 V |
|
Other Input voltage:
|
220 V, 240 V |
|
Number of cables:
|
1 |
|
Input voltage:
|
230 V |
|
Rated power in Watt:
|
800 W |
|
Maximum configurable power in Watt::
|
800 W |
|
Output frequency:
|
50/60 Hz +/- 3 Hz sync to mains |
|
Other Output voltage:
|
220 V, 240 V |
|
Crest factor:
|
03:01:00 |
|
UPS type:
|
Double conversion online |
|
Wave type:
|
Sine wave |
|
Number of power socket outlets:
|
3 IEC 60320 C13 |
|
Bypass type:
|
Internal bypass (automatic and manual) |
|
Curve equation:
|
Efficiency |
|
Curve fixed loss:
|
0.0608 |
|
Curve load maximum:
|
100.00% |
|
Curve load minimum:
|
7.00% |
|
Curve proportional loss:
|
0.0545 |
|
Curve square loss:
|
0.0077 |
|
Curve X-axis maximum:
|
100.00% |
|
Curve test cond ID:
|
Curve fit of data measured in accordance with the ENERGY STAR Test Method for Uninterruptible Power Supplies. All measurements taken in normal mode( s), at typical environmental conditions, with 230V/50Hz electrical input and balanced resistive load (PF = 1.0) output |
|
Curve X-axis minimum:
|
0.00% |
|
Curve X-axis title:
|
Load |
|
Curve X-axis units:
|
Percentage |
|
Curve Y-axis maximum:
|
100.00% |
|
Curve Y-axis minimum:
|
50.00% |
|
Curve Y-axis title:
|
Efficiency |
|
Curve Y-axis units:
|
Percentage |
|
Efficiency:
|
88% (Full Load) |
|
Graph display:
|
1 |
|
Output voltage:
|
230 V |
|
Maximum configurable power in volt-amperes:
|
1000 VA |
|
Rated power in volt-amperes:
|
1000 VA |
|
Runtime at 200W:
|
00:24:00 |
|
Runtime at 400W:
|
00:11:00 |
|
Ambient air temperature for operation:
|
0 to 40°C |
|
Relative humidity:
|
0 to 95% non-condensing |
|
Operating altitude:
|
0 to 3000 m |
|
Ambient air temperature for storage:
|
-20 to 50°C |
|
Storage Relative Humidity Non-condensing:
|
0 to 95% |
|
Storage altitude:
|
0 to 15000 M |
|
Acoustic level:
|
50 dB |
|
Show note OP temperature:
|
No |
|
IP degree of protection:
|
IP20 |
|
Battery type:
|
Lead-acid battery |
|
Number of battery filled:
|
slots 0 |
|
Number of battery free:
|
slots 0 |
|
Battery recharge time:
|
4 H |
|
Additional information:
|
Configurable for 220 : 230 or 240 nominal output voltage |
|
Liquid value:
|
0 |
|
Battery Curve:
|
D |
|
Battery power in VAH:
|
516 VAh runtime |
|
Battery option:
|
SRV36BP-9A 1 1032 VAh, SRV36BP-9A 2 1548 VAh, SRV36BP-9A 3 2064 VAh, SRV36BP-9A 4 2580 VAh, SRV36BP-9A |
|
Package 1 Weight:
|
26.7 Kg |
|
Package 1 Dimension:
|
35.5 x 47 x 52.5 Cm (H x W x D) |
|
Warranty:
|