Batteries & Runtime

Run Time : View Runtime Graph
Efficiency : View Efficiency Graph

APC Easy UPS On-Line SRV 6000VA 230V with Extended Runtime Battery Pack

Serviceability

Automatic self-test : Periodic battery self-test ensures early detection of a battery that needs to be replaced.
Audible alarms : Provides notification of changing utility power and UPS power conditions
Predictive failure notification. : Provides early-warning fault analysis ensuring proactive component replacement.
Disconnected battery notification : Warns when a battery is not available to provide backup power..

Manageability

LCD graphics display : Text and mimic diagrams that display modes of operation, system parameters and alarms..
Serial connectivity : Provides management of the UPS via a serial port .
Intelligent Card Slot : Customize UPS capabilities with management cards.
Network manageable : Most models provide remote power management options of the UPS over the network. Many do not have NMC embedded.
LED Indicators : Provide easy-to-read status of the unit and utility power conditions.
Generator compatible

Ensures clean, uninterrupted power to protected equipment when generator power is used.

ECO Mode

Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection.

Double conversion on-line topology

Guarantees a consistently high level of power quality. Any disturbances on the distribution waveform are regenerated via the zero transfer time AC to DC then DC to AC conversion process. The battery is only used as a back-up source.

Safety-agency approved

Ensures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.

Pure sine wave output on battery

Simulates utility power to provide the highest degree of compatibility for active PFC (power factor corrected) servers and sensitive electronics.

Input power factor correction

Minimizes installation costs by enabling the use of smaller generators and cabling.

Output power capacity : 10.0kWatts / 10.0kVA
Max Configurable Power (Watts) : 10.0kWatts / 10.0kVA
Nominal Output Voltage : 230V
Output Frequency (sync to mains) : 50/60Hz +/- 3 Hz
Other Output Voltages : 220, 240
Load Crest Factor : 3 : 1
Topology : Double Conversion Online
Waveform type : Sine wave